What size breaker do I need for a 20 hp motor?

Motor Horsepower Size Breaker
7-1/2 230V 460V 40 30
10 230V 460V 50 30
15 230V 460V 70 40
20 230V 460V 100 50

How many amps is a 20 hp motor?

AC Motor Full Load Amperes

HP 200 Volts 208 Volts
20 62.1 59.4
25 78.2 74.8
30 92 88
40 120 114

What size breaker do I need for a 21 amp motor?

How to Calculate How What Size Circuit Breaker a Machine will Need:

HorsePower of Main Motor 220 Volts, 1 phase 440 Volts, 3 phase
10 56 14
15 84 21
20 112 28
25 140 35

How do I know what size motor breaker I need?

You must size the conductors at 125% of the motor FLC [430.22(A)]. You must size the overloads no more than 115% to 125% of the motor nameplate current rating, depending on the conditions [430.32(A)(1)]. You must size the short-circuit ground-fault protection device from 150% to 300% of the motor FLC [Table 430.52].

IT IS INTERESTING:  Which Chevy truck engine is best?

How many amps does a 25 hp motor draw?

AMP DRAW BASED ON HORSEPOWER

HP 1 Phase Amps 3 Phase Amps
115 volt 208 volt
15 46.2
20 59.4
25 74.8

How many HP is 15 amps?

Common Amps to Horsepower Conversions

Amps Horsepower Efficiency
10 A 1.45 HP 90%
15 A 2.17 HP 90%
20 A 2.9 HP 90%
25 A 3.62 HP 90%

How do I convert HP to amps?

Converting horsepower to amps can be done in a few simple steps, or using this simple formula.

  1. Amps = (Horsepower × 746) ÷ Efficiency ÷ Volts.
  2. Watts = Horsepower × 746.
  3. Watts = Wattsη
  4. Amps = Watts ÷ Volts.
  5. Amps = HP × 746V × η × PF.

What size breaker do I need for a 5 hp motor?

In fact code recommends a 60 amp circuit breaker for a 5 hp 230v motor, but with overload protection.

How many amps is a 5 hp motor?

A 5 HP motor at 230V, 3PH is12.

Using the formula above, multiply 12.4 amps by 10% for a result of 1.24. Add this total to 12.4 for a total of 13.64 amps.

What size breaker do I need for a 100 hp motor?

Electrical motor wiring data – NEMA amps, starter size, HMCP size for motors ranging 1/2 to 500 hp

Motor HP NEMA amps Motor Circuit Protector type HMCP (ampere)
60 77 150
75 96 150
100 125 200
125 156 250

What size wire do I need for a 1 hp motor?

Single Phase (230 Volt) – Wire Size Selection Guide*
HP Cable Length
1/2 14 14
3/4 14 14
1 14 14

How do you size a 12v fuse?

Find the size of fuse by multiplying the amps required by the device (2) by 1.5. 2×1.25 = 2.5 then we will round up to the nearest fuse size (in multiples of 5 amps) which would call for a 5 amp fuse. Cross Reference that fuse size to verify that it’s below the Maximum fuse size called out by this chart.

IT IS INTERESTING:  Best answer: What is the best black bumper restorer?

How many outlets can be on a 15 amp circuit?

Technically, you can have as many outlets on a 15 amp circuit breaker as you want. However, a good rule of thumb is 1 outlet per 1.5 amps, up to 80% of the capacity of the circuit breaker. Therefore, we would suggest a maximum of 8 outlets for a 15 amp circuit.

How many amps does a 5 HP 3 phase motor draw?

These are only intended to be guidelines and in all cases the full load amps of the motor nameplate should be used for final calculations.

Here are the Full Load Amp (FLA) values for typical 230VAC and 480VAC 3 phase motors.

Motor horsepower Full load amps 230VAC Full load amps 460VAC
3 9 4.5
5 15 7.5
7.5 22 11
10 27 14

How much power does a 2 hp motor use?

How many watts does a 2 HP motors have? If a 2 horse power motor is doing 2 horsepower of work then in the load about 1500 Watts of energy is used in the load.

How much current would a 1.5 HP 240v motor draw?

1 Horsepower is 745.7 watts, so a 1.5 HP motor would require a maximum of 1118.55 watts. 1118.55 W / 220V equals 5.084 amps, so in theory your motor will need just over 5 amps of current.

Service station